Wire Gauge and Voltage Drop Calculator

Sizes a copper conductor for both limits that matter: ampacity, so the cable does not overheat, and voltage drop, so the load actually works.

The current this circuit will actually carry.

Distance to the load, not there and back. The return conductor is counted for you.

3% is the usual target for a branch circuit.

Applies the NEC 690.8(B) 125% factor. Solar output circuits run at full load for hours, so this applies to them.

Recommended conductor

4 AWG

Set by voltage drop. A shorter run or a higher system voltage would allow thinner wire.

Voltage drop
0.25 V (2.1%)
Max overcurrent protection
85 A

This is a floor, not a specification. It does not account for ambient temperature above 30°C, bundling in conduit, or terminal temperature ratings, all of which make the real answer thicker.

How this works

Two independent limits decide what conductor a circuit needs, and they are not the same question.

Ampacity is how much current a conductor carries continuously without its insulation overheating. That is a safety limit. Voltage drop is how much voltage the wire's own resistance consumes on the way to the load. That is a performance limit. This calculator sizes for both and returns whichever is thicker.

It tells you which one decided the answer, because they are fixed by different changes. A voltage drop limit is relieved by shortening the run or raising system voltage. An ampacity limit is not; only reducing the current helps.

Where the numbers come from

Voltage drop uses the round-trip conductor length. Enter the one-way distance to the load and the return path is counted for you, which is a common source of error when doing this by hand.

What this deliberately does not model

Several real factors make the correct conductor thicker than this returns. Treat the result as a floor rather than a specification:

RV and marine wiring

This calculator follows the NEC, which covers buildings in the United States. An RV or a van conversion falls under ANSI/RVIA LV instead, the low voltage standard NFPA 1192 points to, and a boat falls under ABYC. Neither standard's tables are reproduced here, so treat this result as a floor and size to the standard that governs your build. For a boat, Blue Sea's Circuit Wizard works from ABYC's own tables.

For the underlying principles, see off-grid wiring and safety. For why the fuse matters as much as the conductor, see battery safety.